Short answer: On an EICR, C1 means danger is present and needs immediate action. C2 means potentially dangerous and needs urgent action. C3 means improvement is recommended. FI means further investigation is advised. Under BS 7671 Amendment 4, only C1 and C2 make a report unsatisfactory. An FI no longer fails a report on its own.
The four codes at a glance
Every EICR (Electrical Installation Condition Report) ends with a list of observations. Each one gets a code. The codes are set by BS 7671, the UK wiring standard. The version in force since 15 October 2026 is BS 7671:2018+A4:2026, known as Amendment 4.
| Code | Meaning | Makes the report unsatisfactory? | Typical action |
|---|---|---|---|
| C1 | Danger present. Immediate remedial action necessary. | Yes | Made safe at the visit, then repaired |
| C2 | Potentially dangerous. Urgent remedial action necessary. | Yes | Repair booked straight away |
| C3 | Improvement recommended. | No | Plan it in, often with other work |
| FI | Further investigation advised. | Not by itself under Amendment 4 | Investigate to find out what is behind it |
C1: danger present
A C1 means someone could get a shock or a fire could start now. Examples:
- a socket or switch with a cracked or missing cover, exposing live parts
- a ceiling rose with bare live terminals within reach
- a cable with insulation burned or worn through to the copper
- live parts accessible inside a consumer unit with a missing blank
An inspector who finds a C1 will normally make it safe before leaving, for example by switching off and isolating that circuit, and will tell the person responsible. The repair then needs doing.
C2: potentially dangerous
A C2 is not an immediate danger, but would become one if a second thing went wrong. This is the code that most often turns an EICR unsatisfactory. Examples:
- no RCD protection on socket circuits where it is needed (an RCD, residual current device, cuts power within a fraction of a second if current leaks to earth, such as through a person)
- no main protective bonding to the incoming water or gas pipe, or bonding that is too small
- an earth fault loop reading too high, meaning a breaker might not trip fast enough in a fault
- signs of overheating at a terminal or in the consumer unit
- old cable whose insulation is breaking down
Electrical Safety First notes that cables coated in black rubber were phased out in the 1960s. Where that cable turns up and its insulation is crumbling, it is often coded C2.
C3: improvement recommended
A C3 means the installation does not meet today’s standard in some way, but is not considered dangerous. Standards change. Something that was correct when it was installed can be a C3 now. Examples:
- a plastic consumer unit in a home, where new units must now be in a non combustible (usually metal) enclosure
- no surge protection
- labelling missing or out of date
- an older type of socket or switch in good condition
C3 items do not make a report unsatisfactory, and there is no legal deadline to fix them. It is often worth doing them when other work is happening.
FI: further investigation
FI means the inspector found something they could not fully assess during the visit and wants it looked into. Examples:
- a circuit that cannot be traced to where it ends
- an unexpected test reading that needs more time to explain
- a part of the installation that could not be reached
The Amendment 4 change
Before Amendment 4, any FI made the whole report unsatisfactory. NICEIC’s Amendment 4 guidance explains that the observations section is now split in two. The first part holds C1 and C2 items, which decide the result. The second part holds C3 and FI items, which do not. The wording of FI has also changed: it used to say “without delay”, and that has been removed.
NICEIC says the reason is that FI was sometimes used where not enough time had been allowed for the inspection, or as a way to come back for more work without evidence. The change is meant to make reports more accurate.
For landlords, read this alongside the law. The government guidance says remedial or further investigative work shown as necessary in the report must be done within 28 days. So an FI is still something to book, even if the report is satisfactory.
A worked example
Picture a Victorian terrace converted into two flats, the kind found across Hackney and Wandsworth. The lower flat’s EICR might read:
- C2: socket circuit in kitchen not RCD protected
- C2: main bonding to gas pipe missing
- C3: plastic consumer unit
- C3: no surge protection
- FI: lighting circuit 3 could not be traced fully, may pass through upper flat
Result: unsatisfactory, because of the two C2 items. The landlord needs both C2s repaired, and the FI investigated, within 28 days. Often the fix for the first C2 is a new consumer unit with RCD protection, which also clears the plastic board C3. That is notifiable work under Part P. See our consumer unit replacement page, and our Hackney page for more on converted flats there.
Reading your own report
- Turn to the summary and check the overall result.
- Read every observation and its code.
- Ask the inspector to explain anything you do not understand, in plain terms.
- Ask for written prices for C1, C2 and FI work.
- If you are a landlord, follow the steps in EICR unsatisfactory: what next.
Our EICR page explains how we carry out inspections and price repairs after the report.
Quick questions
What is a C2 on an EICR?
A C2 is an observation that is potentially dangerous. It is not dangerous right now, but could become so if something else goes wrong, such as a fault on an appliance. It needs urgent repair and makes the report unsatisfactory.
How long do I have to fix a C2?
For landlords in England, remedial work must be done within 28 days of the inspection, or a shorter time if the report says. Owner occupiers have no legal deadline, but should treat a C2 as urgent.
Does a C3 mean I failed?
No. A C3 is a recommendation. Many older homes have several C3s, for example sockets without RCD protection in a place where the standard has since changed.
Why did FI change under Amendment 4?
NICEIC explains that FI was sometimes used where an inspector had not allowed enough time, or to create follow up work. Amendment 4 moved FI into a separate part of the report so it no longer decides the overall result.